900 W
Single phase 2 wires and Ground
110VAC – 290VAC 110-160VAC on 30% load, 160-200VAC on 80% load 200-290VAC on 100% load
45Hz-55Hz(Auto Detect)
>0.99
<7%(100% nonlinear load)
Max.voltage: +15%(optional +5%, +10%, +25%) Min. voltage: -45% (optional -20%, -30%) Frequency protection range: ±10%
Max.voltage: +15%(optional +5%, +10%, +25%) Min. voltage: -45% (optional -20%, -30%) Frequency protection range: ±10%
Support
±2%
Single Phase & Ground
200/208/220/230/240VAC
Pure sine wave
0.9
50Hz or 60Hz (Synchronized to Mains)
50Hz/60Hz ±0.02Hz
3:1
<3% with linear load <5% with non linear load
36VDC
Full load.3-5 min(Standard) Estimated remaining time displayed on the LCD
12V/7AH
0°C~40°C
-25°C~55°C
0~95% non condensing
Load150% : 300mS then shut
Load Less Then 100% – 150% : 30Seconds, Greater Then 150% : 300mS then shut
Supports Windows family, Linux, FreeDSB etc.
SNMP card, Dry Contact card
Built in Power Surge, Lightning Device
Up to 89%
>94%
440×86.5×410
12
IEC320 C14-10A
IEC320 C13-10Ax6
Anderson like PowerPole Modular connectors
CE,CB