EHY-A10000MP
Series: EHY
Capacity: 10000 W

Description

  • Micro Processor Control
  • Pure Sine Wave
  • Intelligent Battery Management
  • Rapid Charging
  • Power Factor 0.8
Technical
Capacity 10000 W
Maximum Charging Power 9600 W
Phase 3-phase in / 3-phase out
Environment
Operating Temperature -10 to 55°C
Humidity 0 ~ 90% RH (No condensing)
Altitude 0 ~ 1000 m*
Physical
Dimension, D x W x H (mm) 622 x 500 x 167.5
Net Weight (kgs) 45
Internal Resistance
Communication Port RS-232/USB and CAN Interface
Intelligent Slot Optional SNMP, Modbus, and AS-400 cards available
Grid PV Input (DC)
Maximum PV Input Power 14850W
Nominal DC Voltage / Maximum DC Voltage 720 VDC / 900 VDC
Start-up Voltage / Initial Feeding Voltage 320 VDC / 350 VDC
MPP Voltage Range 350 VDC ~ 850 VDC
Number of MPP Trackers / Maximum Input Current 2 / 2 x 18.6A
Grid Output (AC)
Nominal Output Voltage 230 VAC (P-N) / 400 VAC (P-P)
Output Voltage Range 184 - 265 VAC per phase
Nominal Output Current 14.5 A per phase
Power Factor > 0.99
Grid Efficiency
Maximum Conversion Efficiency (DC/AC) > 96%
European Efficiency@ Vnominal > 95%
Off-Grid AC Input
AC Start-up Voltage/Auto Restart Voltage 120 - 140 VAC per phase / 180 VAC per phase
Maximum AC Input Current 25A
Acceptable Input Voltage Range 170 - 280 VAC per phase
Off-Grid PV Input (DC)
Maximum DC Voltage 900 VDC
MPP Voltage Range 350 VDC ~ 850 VDC
Number of MPP Trackers / Maximum Input Current 2 / 2 x 18.6A
Off-Grid Battery Mode Output (AC)
Nominal Output Voltage 230 VAC (P-N) / 400 VAC (P-P)
Output Waveform Pure Sinewave
Efficiency (DC to AC) 91%
Hybrid PV INPUT (DC)
Start-up Voltage / Initial Feeding Voltage 320 VDC / 350 VDC
Nominal DC Voltage / Maximum DC Voltage 720 VDC / 900 VDC
MPP Voltage Range 350 VDC ~ 850 VDC
Number of MPP Trackers / Maximum Input Current 2 / 2 x 18.6A
Hybrid AC Input
Acceptable Input Voltage Range 170 - 280 VAC per phase
AC Start-up Voltage / Auto Restart Voltage 120 - 140 VAC per phase / 180 VAC per phase
Maximum AC Input Current 25A
Hybrid Grid Output (AC)
Nominal Output Voltage 230 VAC (P-N) / 400 VAC (P-P)
Output Voltage Range 184 - 265 VAC per phase
Nominal Output Current 14.5 A per phase
Hybrid Battery Mode Output (AC)
Efficiency (DC to AC) 91%
Hybrid Battery & Charger
Nominal DC Voltage 48 VDC
Maximum Charging Current Default 60A, 5A - 200A (Adjustable)